Date: 1/21/2011 Time: 03:30 PM Report ID: 1121119
Property:
 
Customer:
 
Real Estate Professional:

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

In Attendance:
Customer and Seller

Type of building:
Multi-family

Approximate age of building:
Over 50 Years

Temperature:
Below 32

Weather:
Cloudy

 
Top Table of Contents Bottom

Styles & Materials
Viewed roof covering from:
Ground
Roof-Type:
Hip
Roof Ventilation:
Ridge vents
Soffit Vents
Method used to observe attic:
From entry
Roof Structure:
Engineered wood trusses
Plywood
Ceiling Structure:
4" or better
Attic Insulation:
Blown
Fiberglass
Cellulose
Below
R-19
Attic info:
Scuttle hole
Method used to observe Crawlspace:
From entry
Foundation:
Poured concrete
Columns or Piers:
Conrete piers
Floor Structure:
2 X 10
Wood joists
Floor System Insulation:
NONE
Wall Structure:
2 X 4 Wood
Chimney (exterior):
Brick
Inspection Items
A. Foundations (If all crawlspace areas are not inspected, provide an explanation.)
Comments: Inspected, Repair or Replace
Several of the screens in the crawl space vents are torn that will allow mice to enter the crawlspace.(Picture 1)
A. Picture 1
B. Columns and Piers
Comments: Inspected
C. Grading and Drainage
Comments: Inspected, Repair or Replace
There is a negative slope towards the front (right of main entry) and (North side of home). This area does not appear to drain water away from home and needs landscaping and drainage corrected.(Picture 1)(Picture 2)

The opening at the northwest entry needs to be sealed.(Picture 3)

C. Picture 1
C. Picture 2
C. Picture 3
D. Roof Covering (If the roof is inaccessible, report the method used to inspect)
Comments: Inspected, Repair or Replace
There is a large amount of ice damming on roofs in concentrated sections of the roofs. This is caused by heat loss in these areas.The ice damming at the south center side has pulled the soffit loose at this location.(Picture 1) (Picture 2)

The attic insulation is only 6'' average. I would recommend installing 6' more insulation to prevent ice damming and heat loss.

Several of the gutter downspouts are missing.(Picture 3)

The sewer vent flashing above  unit #77 is leaking into the attic.(Picture 4)

D. Picture 1
D. Picture 2
D. Picture 3
D. Picture 4
E. Roof Structure and Attic (If the attic is inaccessible report the method used to inspect.)
Comments: Inspected, Repair or Replace
The trees at the north west corner needs to be trimmed away from the building and the roof.(Picture 1)
E. Picture 1
F. Walls (Interior and Exterior)
Comments: Inspected
G. Ceilings and Floors
Comments: Inspected, Repair or Replace
All of the missing drywall in the basement boiler rooms and storage rooms needs to be replaced to maintain the fire rated ceilings.(Picture 1)
G. Picture 1
H. Doors (Interior and Exterior)
Comments: Inspected
The exterior doors are in good condition.The veneer on door #78 is delaminating.(Picture 1)
H. Picture 1
I. Windows
Comments: Inspected, Repair or Replace
90 % of window glass has broken insulated glass seals.

The aluminum windows are very low efficiency ,the frames and the sash don't seal tight.(Picture 1)

I. Picture 1
K. Porches, Decks and Carport (Attached)
Comments: Inspected, Repair or Replace
The upper deck floor joist have has structural dryrot.New joist have been sistered next to the old one but they have not been supported back into the wall.(Picture 1)

At the base of all the steel handrails , the concrete needs to be seals with a urithane caulking to prevent further rust.(Picture 2)

K. Picture 1
K. Picture 2
Top Table of Contents Bottom

Styles & Materials
Electrical Service Conductors:
Below ground
Aluminum
220 volts
Panel Type:
Circuit breakers
Electric Panel Manufacturer:
BRYANT
SQUARE D
Branch wire 15 and 20 AMP:
Copper
Wiring Methods:
Romex
 
Inspection Items
A. Service Entrance and Panels
Comments: Inspected
B. Branch Circuits - Connected Devices and Fixtures (Report as in need of repair the lack of ground fault circuit protection where required.)
Comments: Inspected, Repair or Replace
There is several extension cords in the boiler rooms that should be wired in a conduit.(Picture 1)(Picture 2)
B. Picture 1
B. Picture 2
C. Smoke Detector
Comments: Inspected, Repair or Replace
The smoke detector should be tested at common hallway to bedrooms .

There is no carbon monoxide detector found in home. It is recommended that one be installed according to the manufacturer's instructions.
Top Table of Contents Bottom

Styles & Materials
Type and Energy Source:
Circulating boiler
Energy Source:
Natural gas
Number of Heat Systems (excluding wood):
Two
Inspection Items
A. Heating Equipment
Comments: Inspected, Repair or Replace
The wires to the pump on the boiler in unit # 3465 needs to be a flexible connection. (Picture 1)   The wires are loose at this time.

There is a few leaking heating pipe fittings.(Picture 2)

All of the heating pipes in the basement and crawl space should be insulated.

Two of the heating circulating pumps on the boilers in the southwest boiler room are leaking.(Picture 3) And the presser relief valve is leaking.(Picture 4) on the boiler.

The boilers in both of the units are old and at the end of there life expectancy.The efficiency of the boilers are very low.

A. Picture 1
A. Picture 2
A. Picture 3
A. Picture 4
Top Table of Contents Bottom

Styles & Materials
Water Source:
Public
Plumbing Water Supply (into home):
Copper
Plumbing Water Distribution (inside home):
Copper
Plumbing Waste:
PVC
Cast iron
Water Heater Power Source:
Gas (quick recovery)
 
Inspection Items
A. Water Supply System and Fixtures
Comments: Inspected, Repair or Replace
The lawn sprinkler line should be a ridge pipe and not hung from a heating pipe.(Picture 1)
A. Picture 1
B. Drains, Waste, Vents
Comments: Inspected, Repair or Replace
Several of the bath tub drains are corroded and are leaking.(Picture 1)

Most of the drain lines in the basement and crawl are old galvanized pipe.(Picture 2)

B. Picture 1
B. Picture 2
C. Water Heating Equipment (Report as in need of repair those conditions specifically listed as recognized hazards by TREC Rules
Comments: Inspected, Repair or Replace
The water boiler in unit #3465 is leaking.(Picture 1)
C. Picture 1
D. Sump Pump
Comments: Inspected, Repair or Replace
The sump pump drain tile lines are parcels blocked with mineral deposits and should be cleaned.(Picture 1)
D. Picture 1
E. Main Water Shut Off (Describe Location)
Comments: Inspected
G. Gas Piping Fuel Storage
Comments: Inspected

Prepared Using HomeGauge
http://www.HomeGauge.com : Licensed To Van Wert Inspections
Top Table of Contents Bottom
 

General Summary


Van Wert Inspections

4418 South Nine Mile Road
Auburn Mi 48611
989-662-9378

Customer
90-Unit Apartment Complex

Address
Michigan

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

I.  STRUCTURAL SYSTEMS
A.   Foundations (If all crawlspace areas are not inspected, provide an explanation.)  
  Inspected, Repair or Replace  
Several of the screens in the crawl space vents are torn that will allow mice to enter the crawlspace.(Picture 1)
C.   Grading and Drainage  
  Inspected, Repair or Replace  
There is a negative slope towards the front (right of main entry) and (North side of home). This area does not appear to drain water away from home and needs landscaping and drainage corrected.(Picture 1)(Picture 2)

The opening at the northwest entry needs to be sealed.(Picture 3)

D.   Roof Covering (If the roof is inaccessible, report the method used to inspect)  
  Inspected, Repair or Replace  
There is a large amount of ice damming on roofs in concentrated sections of the roofs. This is caused by heat loss in these areas.The ice damming at the south center side has pulled the soffit loose at this location.(Picture 1) (Picture 2)

The attic insulation is only 6'' average. I would recommend installing 6' more insulation to prevent ice damming and heat loss.

Several of the gutter downspouts are missing.(Picture 3)

The sewer vent flashing above  unit #77 is leaking into the attic.(Picture 4)

E.   Roof Structure and Attic (If the attic is inaccessible report the method used to inspect.)  
  Inspected, Repair or Replace  
The trees at the north west corner needs to be trimmed away from the building and the roof.(Picture 1)
G.   Ceilings and Floors  
  Inspected, Repair or Replace  
All of the missing drywall in the basement boiler rooms and storage rooms needs to be replaced to maintain the fire rated ceilings.(Picture 1)
I.   Windows  
  Inspected, Repair or Replace  
90 % of window glass has broken insulated glass seals.

The aluminum windows are very low efficiency ,the frames and the sash don't seal tight.(Picture 1)

K.   Porches, Decks and Carport (Attached)  
  Inspected, Repair or Replace  
The upper deck floor joist have has structural dryrot.New joist have been sistered next to the old one but they have not been supported back into the wall.(Picture 1)

At the base of all the steel handrails , the concrete needs to be seals with a urithane caulking to prevent further rust.(Picture 2)


II.  ELECTRICAL SYSTEMS
B.   Branch Circuits - Connected Devices and Fixtures (Report as in need of repair the lack of ground fault circuit protection where required.)  
  Inspected, Repair or Replace  
There is several extension cords in the boiler rooms that should be wired in a conduit.(Picture 1)(Picture 2)
C.   Smoke Detector  
  Inspected, Repair or Replace  
The smoke detector should be tested at common hallway to bedrooms .

There is no carbon monoxide detector found in home. It is recommended that one be installed according to the manufacturer's instructions.

III.  HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS
A.   Heating Equipment  
  Inspected, Repair or Replace  
The wires to the pump on the boiler in unit # 3465 needs to be a flexible connection. (Picture 1)   The wires are loose at this time.

There is a few leaking heating pipe fittings.(Picture 2)

All of the heating pipes in the basement and crawl space should be insulated.

Two of the heating circulating pumps on the boilers in the southwest boiler room are leaking.(Picture 3) And the presser relief valve is leaking.(Picture 4) on the boiler.

The boilers in both of the units are old and at the end of there life expectancy.The efficiency of the boilers are very low.


IV.  PLUMBING SYSTEM
A.   Water Supply System and Fixtures  
  Inspected, Repair or Replace  
The lawn sprinkler line should be a ridge pipe and not hung from a heating pipe.(Picture 1)
B.   Drains, Waste, Vents  
  Inspected, Repair or Replace  
Several of the bath tub drains are corroded and are leaking.(Picture 1)

Most of the drain lines in the basement and crawl are old galvanized pipe.(Picture 2)

C.   Water Heating Equipment (Report as in need of repair those conditions specifically listed as recognized hazards by TREC Rules  
  Inspected, Repair or Replace  
The water boiler in unit #3465 is leaking.(Picture 1)
D.   Sump Pump  
  Inspected, Repair or Replace  
The sump pump drain tile lines are parcels blocked with mineral deposits and should be cleaned.(Picture 1)


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Van Wert Inspections

Top Table of Contents Bottom
 

Van Wert Inspections

Larry Van Wert
4418 South Nine Mile Road
Auburn Mi 48611
989-662-9378
Top Table of Contents Bottom
 

Inspection Agreement

(PLEASE READ CAREFULLY)

Van Wert Inspections agrees to conduct an inspection for the purpose of informing the CLIENT of major deficiencies in the condition of the property, subject to the UNCONDITIONAL RELEASE AND LIMITATION OF LIABILITY below.  The inspection and report are performed and prepared for the sole, confidential and exclusive use and possession of the CLIENT.   The report will only include the following: 

  • Structural condition and basement
  • Electrical, plumbing, water heater, heating and cooling
  • Quality, condition and life expectancy of major systems
  • Kitchen and appliances
  • General interior, including ceilings, walls, windows, insulation and ventilation
  • General exterior, including roof, gutter, chimney, drainage, grading

It is understood and agreed that this inspection will be of readily accessible areas of the building and is limited to visual observations of apparent conditions existing only at the time of the inspection.  Latent and concealed defects and deficiencies are excluded from the inspection; equipment, items, and systems will not be dismantled.

Maintenance and other items may be discussed, but they are not a part of our inspection.   The report is not a compliance inspection or certification for past or present governmental codes or regulations of any kind. 

The inspection and report do not address and are not intended to address the possible presence of or danger from any potentially harmful substances and environmental hazards, including but not limited to radon gas, lead paint, asbestos, mold, mildew, urea formaldehyde, toxic or flammable chemicals, and water and airborne hazards.   Also excluded are inspections of and reports on swimming pools, wells, septic systems, security systems, central vacuum systems, water softeners, sprinkler systems, fire and safety equipment, and the presence or absence of rodents, termites and other insects.

UNCONDITIONAL RELEASE AND LIMITATION OF LIABILITY

It is understood and agreed that Van Wert Inspections is not an insurer and that the inspection and reports are not to be intended or construed as a guarantee or warranty of the adequacy, performance, or condition of any structure, item, or system at the property address.   The CLIENT hereby releases and exempts Van Wert Inspections and its employees of and from all liability and responsibility for the cost of repairing or replacing any unreported defect or deficiency and for any consequential damage, property damage, or personal injury of any nature.

In the event that Van Wert Inspections and/or its employees are found liable due to breach of contract, negligence, negligent misrepresentation, negligent hiring or any other theory of liability, then the liability of Van Wert Inspections and employees shall be limited to a sum equal to the amount of the fee paid by the CLIENT to Van Wert Inspections for the inspection and report.

CLIENT and Van Wert Inspections agree that should a court of competent jurisdiction determine and declare that any portion of this Agreements is void, voidable or unenforceable, the remaining provision and portion shall remain in full force and effect.

Acceptance and understanding of this agreement are hereby acknowledged:

 

________________________________     _________________________________

Company Representative           Date                   Client                                                      Date 

Top Table of Contents Bottom